Sample plc–5/250 program (cont’d) – Rockwell Automation 5370 Color CVIM Communications Manual User Manual

Page 145

Advertising
background image

Chapter 6
Using the Pyramid Integrator Backplane

6–8

5370–CVIMC EXAMPLE PROGRAM
Program Listing Report PLC–5/250 File CVIMC

Rung 1TRN0:0
| |
+–[AFI]––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––[EOT]–+
| |

Rung 1TRN0:1
| |
+––––––––––––––––––––––––––––––––[END OF FILE]–––––––––––––––––––––––––––––––––+
| |

Rung 1STEP0:0
| 5370–CVIMC |
| REQUEST |
| 5370–CVIMC 100 MILLI– |
| REQUEST SECOND |
| WORD TIMER |
| +CMP–––––––––––––––+ +TON–––––––––––––––+ |
+–+COMPARE +––––––––––––––––––––––––+–––––+TIMER ON DELAY +–(EN)+–+
| |Expression | | |Timer 1T0:0| | |
| |1N0:0<>0 | | |Time base 0.01+–(DN)| |
| +––––––––––––––––––+ | |Preset 10| | |
| | |Accum 0| | |
| | +––––––––––––––––––+ | |
| | 5370–CIMVC | |
| | ONE SHOT | |
| | MESSGAGE | |
| | ACTIVATION | |
| | BIT | |
| |+OSR––––––––––––––––––––+ | |
| ++ONE SHOT RISING +–(OB)+ |
| |Output Bit 1N0:1/0| |
| |Storage Bit 1N0:1/1+–(SB) |
| +–––––––––––––––––––––––+ |

Rung 1STEP0:1
| 5370–CVIMC|5370–CVIMC|5370–CVIMC |
| 100 MILLI–|100 MILLI–|100 MILLI– |
| SECOND |SECOND |SECOND 5370–CVIMC |
| TIMER |TIMER |TIMER REQUEST |
| ENABLED |TIMING |DISABLED WORD |
| 1T0:0 1T0:0 1T0:0 +CLR–––––––––––––––+ |
+––––] [––––––––]/[––––––––] [––––––––––––––––––––––––––––+CLEAR +–+
| EN TT DN |Dest 1N0:0| |
| | 0| |
| +––––––––––––––––––+ |

Rung 1STEP0:2
| 5370–CVIMC 5370–CVIMC |
| TRIGGER HOST |
| INSPECTION TRIGGER |
| REQUEST TOOLSET |
| BIT BIT |
| 1N0:0 1SD13:1023 |
+––––] [–––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––( )–––––+
| 0 10 |

Sample PLC–5/250 Program
(cont’d)

Advertising