2 point tuning – KEYENCE IL Series User Manual

Page 46

Advertising
background image

3-4 Setting the Tolerance Setting Value

3-14

3

Basic Oper

ations

IL-E

2 point tuning

With this method, the median value of the good target and defective target is set as the
tolerance setting value when there are good target and HIGH/LOW defective target.

1

Press the W / X button several times on the main screen. Then display the
HIGH side setting value on the sub display (lower level).

"Sub Display (Lower Level)" (page 3-4)

2

Measure the good target and press the [SET] button. (HIGH side 1st point
confirmation operation)

The internal measurement value (R.V.) is imported as a good target measurement value.
[Hiset] is displayed on the main display (upper level).

3

Measure the HIGH side defective target and press the [SET] button. (HIGH
side 2nd point confirmation operation)

The internal measurement value (R.V.) is imported as a measurement value for
HIGH side defective target.
After [set] blinks on the main display (upper level), the judgment value (P.V.) is
displayed.
On the sub display (lower level), the median value of the good target value (1st point)
imported on step 5 and HIGH defective target value (2nd point) is displayed.
Setting the HIGH side setting value (upper limit) is complete.

4

Press the X button once and display the LOW side setting value on the sub
display (lower level).

Reference

When the tuning result exceeds the setting range, the limit value of the
setting range becomes the setting value.

Point

Two-point tuning is not performed if the internal measurement value
(R.V.) is [
-----].
If performed, [
no.uaL] will blink several times on the main display.

GO



LASER

BANK

0

1

2

3

HI

LO

R.V.

ANALOG

HI

SHIFT

ZERO SHIFT

TIMING

LO

ALIGNMENT



HOLD

CALC

CHECK

[HI]

ON

HIGH side setting value



LOW side setting value

[LO]

ON

Advertising