2.4 Instruction Details

1

2

3-97

Chapter 2 Instructions

Description

W-ON

When input relay 0000 is ON, output operand 1000 turns ON as soon as the
contact of input operand 0001 turns ON.

W-OFF

When input relay 0002 is ON, output operand 1001 turns ON as soon as the
contact of input operand 0003 turns OFF.

Note: Output operand relay Nos. for W-ON/W-OFF instructions cannot be dupli-
cated in a program.

Operands

*

Note that of I/O Nos. 7000 to 9915, those that are not assigned to expansion or
remote I/O unit ports can be used for internal utility relays.

Key operation

0002

0003

1001

0002

0003

OFF

1001

1001

0000

0001

1000

0000

0001

ON

1000

1000

Same
operation

Input operand

Output operand

W-ON

F

W-OFF

L i

First operand

(nnnn)

Second operand

(mmmm)

ENT

R-SRCH

Same
operation

Input operand

Output operand

W-ON / W-OFF

Visual KV

KV-300

KV-10/16

KV-24/40/80

nnnn:

nnnn:

nnnn:

nnnn:

0000 to 17915

0000 to 0009

0000 to 2915

0000 to 6915

T000 to T249

0500 to 17915

T000 to T063

T000 to T119

C000 to C249

T000 to T249

C000 to C063

C000 to C119

CTC0 to CTC3

C000 to C249

CTC0 to CTC3

CTC0 to CTC3

mmmm:

CTC0 to CTC3

mmmm:

mmmm:

1000 to 1915

mmmm:

1000 to 1915

1000 to 1915

3000 to 9915

1000 to 1915

3000 to 6915

3000 to 6915

*7000 to 9915