7.2 Serial Communication

3-308

7

Chapter 7 Serial Communication

7.2

Serial Communication

When the KV is connected to a personal computer, the current value or preset value
of timers/counters or contents of data memories in the KV can be loaded to and
modified on the computer.

7.2.1

Command Transmission Procedure

Commands are transmitted from a personal computer to the KV base unit as follows:

Transmitting a break signal
A break signal is used to initialize the communication buffer and baud rate setting of
the KV. It is necessary to transmit a break signal of 100 ms or longer to the KV
before starting communication. Another break signal is unnecessary once the
communication is established.
A break signal must have the waveform shown below.

Note 1: For the first serial communication with a personal computer after the KV-
P3E(01) handheld programmer is connected to the KV, or after the "KV IncrediWare
(DOS)" or "LADDER BUILDER for KV" programming support software is evoked, be
sure to transmit a break signal. A break signal is unnecessary at other times.
Note 2: If you cannot transmit a break signal, turn OFF the KV once to initialize the
communication program. After that, restart communication between the KV and the
personal computer.
Note 3: Be sure to stop the communication for 10 ms or longer after transmitting a
break signal.

10 ms or longer

Transmits a command

Transmits communications
start command (CR)

Initialize the communication buffer and
baud rate setting of the KV.

Start communications with the KV.

Transmit a command which instructs the
KV to perform the required operation.

Transmits communications
end command (CQ)

End communications with the KV.

Receive and check the response to the
transmitted command.

Transmits a break signal

Receiving a response

100 ms or longer

+V

-V

SD

KVNKA Chap 07.p65

08.3.11, 0:11 PM

308