7.2 Serial Communication

3-313

1

7

Chapter 7 Serial Communication

Reading DM
Reads the contents of the specified data memory.

Command: RD_DMnnnn

Data memory No.

Response: ddddd

Data in the specified data memory. (00000 to
65535: in decimal)

Reading TM
Reads the contents of the specified temporary data memory.

Command: RD_TMnn

Temporary data memory No. (00 to 31)

Response: ddddd

Data in the specified temporary data memory.
(00000 to 65535: in decimal)

Writing current value of counter
Changes the current value of the specified counter or up-down counter.

Command: WR_Cnn_ddddd

New current value (00000 to 65535: in decimal)
Counter No.

Response: OK

Writing current value of timer
Changes the current value of the specified timer.

Command: WR_Tnnn_ddddd

New current value (00000 to 65535: in decimal)
Timer No.

Response: OK

Writing current value of high-speed counter CTH
Changes the current value of the specified high-speed counter CTH.

Command: WR_CTHn_ddddd

New current value (00000 to 65535: in decimal)
High-speed counter No.

Response: OK

Writing preset value of counter
Changes the preset value of the specified counter or up-down counter.

Command: WS_Cnnn_ddddd

New preset value (00000 to 65535: in decimal)
Counter No.

Response: OK

Note: Executing this command changes the program in the KV. The program in EEPROM is
automatically updated the next time the KV is turned ON.

Writing preset value of timer
Changes the preset value of the specified timer.

Command: WS_Tnnn_ddddd

New preset value (00000 to 65535: in decimal)
Timer No.

Response: OK

Note:

Visual KV Series:

Executing this command changes the program in the KV. The
program in EEPROM is automatically updated the next time the KV
is turned ON.

KV-300, 10/80 Series:

The "WS" command changes the content of the program
stored in the PLC’s EEPROM.

➮ Contact Keyence if you need to change it frequently.