Cmp: compare @cmp: compare – KEYENCE Visual KV Series User Manual

Page 170

Advertising
background image

2.4 Instruction Details

3-146

2

Chapter 2 Instructions

CMP instruction compares the contents of the internal register with the value speci-
fied by the operand, and turns ON/OFF the special utility relays (2009, 2010, 2011)
according to the result of comparison.

Comparing the current value of the counter and CMP value

1) Output relay 0500 turns ON when the counter value is smaller than "1000" (C001

< #01000).

2) Output relay 0501 turns ON when the counter value is equal to "1000" (C001 =

#01000).

3) Output relay 0502 turns ON when the counter value is greater than "1000" (C001

> #01000).

4) Output relay 0503 turns ON when the counter value is equal to or greater than

"2000" (C001 ≥ #02000).

Coding

CMP: Compare

@CMP: Compare

Compares contents of internal register with
value specified by operand.

@

#,$

FUN

FUN

LDB

4

RES

0

LDB

4

RES

0

nnnn
CMP

nnnn
CMP

2009

2010

2011

(Internal register) < (Operand)

ON

OFF

OFF

(Internal register) = (Operand)

OFF

ON

OFF

(Internal register) > (Operand)

OFF

OFF

ON

0001

C001

LDA

#01000

CMP

0500

#09999

0003

C001

2) (=)

1) (<)

3) (>)

4) (≥)

2002

C001

LDA

#02000

CMP

2002

2009

0501

2010

0502

2011

0503

2009

Line No.

Instruction

Operand

Line No.

Instruction

Operand

0000

LDB

0001

0012

OUT

0501

0001

C

001 #099999 0003

0013

MPP

0002

LD

2002

0014

AND

2011

0003

LDA

C001

0015

OUT

0502

0004

CON

0016

LD

2002

0005

CMP

#01000

0017

LDA

C001

0006

CON

0018

CON

0007

MPS

0019

CMP

#02000

0008

AND

2009

0020

CON

0009

OUT

0500

0021

ANB

2009

0010

MRD

0022

OUT

0503

0011

AND

2010

:

:

CMP / @CMP

KVNKA Chap 02_4cP.p65

08.3.11, 0:02 PM

146