2.4 Instruction Details

1

2

3-103

Chapter 2 Instructions

Example

Coding

Description

When input relay 0000 is ON:
0500 turns ON as soon as 0001 turns ON.
0501 turns ON as soon as 0002 turns ON.
0502 turns ON as soon as 0003 turns ON.

The MPS instruction is used at the start of an output branch.

The MRD instruction is used to connect an output branch.

The MPP instruction is used at the end of an output branch.

When the KV IncrediWare (DOS)/LADDER BUILDER for KV programming
support software is used, the MPS, MRD, and MPP instructions are automatically
converted into mnemonics and entered in the ladder diagram.

Note 1: Limit the number of MPS instructions to 8 or less in a circuit.

Note 2: An MPS instruction must have a corresponding MPP instruction. This
means that the same number of MPS and MPP instructions must be used in a
program. An MPS or MPP instruction without a corresponding MPP or MPS instruc-
tion results in a logic error.

Operands

Key operation

MPS: Push

MRD: Read

MPP: Pop

Stores current input and arithmetic flag
status.

Reads input and arithmetic flag status
stored with PUSH.

Reads and clears input and arithmetic flag
status stored with PUSH.

Line No.

Instruction

Operand

0000

LD

0000

0001

MPS

0002

AND

0001

0003

OUT

0500

0004

MRD

0005

AND

0002

0006

OUT

0501

0007

MPP

0008

AND

0003

0009

OUT

0502

MPS

C

MRD

D

MPP

c h

0000

0501

0500

0001

0002

0003

0502

MRD

MPP

MPS

MPS

C

MRD

D

MPP

ch

ENT

R-SRCH

:

:

:

MPS / MRD / MPP