5.3 Examples of Using the Positioning Control Function

Visual KV

Series

1

5

Chapter 5 Positioning Control

3-259

5.3.3

Application Examples of the Positioning Control
Function

Ladder example of ramp-up/down control

When start switch 0000 is set to ON, output 0502 starts to output 100,000 pulses
with a startup frequency of 500 Hz, operating frequency of 10 kHz, and acceleration/
deceleration time of 3 seconds.
When input 0001 is set to ON, pulse output is decelerated and stopped.
When input 0002 is set to ON, pulse output is immediately stopped.

Program example

0

100000

500

1000

Speed (Hz)

Coordinate (pulses)

Permit interrupts when operation is
started (so that emergency stop
operations are available).

2008

2002

EI

0001

0002

0003

0004

0005

0006

0007

0008

0009

#34464

DW

#00001

DW

#03000

DW

#10000

DW

#00500

DM1484

DM1485

DM1482

DM1481

DM1480

DW

0000

2309

RES

2310

0001

2308

RETI

ENDH

END

INT

0002

HSP

0002

2002

Set the input time constant of input
0002 to 10 µs.

Set each parameter, and start pulse
output at the same time.

Decelerate and stop pulse output.

Perform emergency stop processing
by using an interrupt program.