1 before creating programs, 1 flow from introduction to operation – KEYENCE Visual KV Series User Manual

Page 26

Advertising
background image

1.1 Before Creating Programs

3-2

1

Chapter 1 Programming

1.1

Before Creating Programs

This section describes what you should know before creating programs and opera-
tions for the Visual KV Series.

1.1.1

Flow from Introduction to Operation

This section describes an overview of program creation procedures, functions used,
and setting items.
In the example described below, a latch circuit is created as a program for the Visual
KV Series.

Introduction

Examining contents of operations

Figure 1 shows a latch circuit which operates as follows.

Pushbutton switch PB1: ON
Pushbutton switch PB2: OFF

➞Pilot lamp (PL) turns on.

Pushbutton switch PB1: OFF
Pushbutton switch PB2: OFF

➞Pilot lamp (PL) remains

lit even if PB1 turns
OFF.

Pushbutton switch PB1: OFF
Pushbutton switch PB2: ON

➞Pilot lamp (PL) goes out

when PB2 is set to ON.

Time chart

ON

OFF

ON

OFF

PL

ON

OFF

PB1 contact

PB2 contact

Fig. 1
PB1 = N.O. contact switch
PB2 = N.C. contact switch

PB1

PB2

RL

(Relay)

PL

Next, a program is created that will use the same operation as this circuit to control a PLC.

Program examination

Circuit 1 shows relay symbols for the latch circuit.
Examine which contact in the Visual KV Series is used for each pushbutton switch and pilot lamp
(Table 1). When many I/O devices are required for control, expansion units should also be considered.

Circuit 1

PL

RL

RL

RL

PB1

PB2

Relay (coil)

Relay (contact)

Relay (contact)

Pilot lamp

Table 1

I/O device

Contact No.

Pushbutton switch PB1 (N.O. contact)

Input relay (0000)

Pushbutton switch PB2 (N.C. contact)

Input relay (0001)

Relay RL

Internal relay (1000)

Pilot lamp PL

Output coil (0500)

Program creation

Edit a program using the "LADDER BUILDER for KV" programming support software creation tool.

Ladder diagram

0500

1000

1000

1000

0000

0001*

Coding list
LD

0000

OR

1000

AND

0001

OUT

1000

LD

1000

OUT

0500

END

* Enter "N.O. (AND X001)" to 0001 to

use N.C. contact.

Transferring and confirming the program

Transfer the created program to the Visual KV Series, perform a test run, and then confirm operations
with the actual devices.

Operation

KVNKA Chap 01P.p65