6.2 High-speed Counters

KV

-300

KV-10/80

3-285

1

6

Chapter 6 Interrupts, High-speed Counters, Positioning Control

0000

2105

0000

SET

2105

RES

0000

2105

0000

SET

RES

KEEP

KEEP Instructions

SET/RES Instructions

Coding

Line No.

Instruction

Operand

0000

LD

2008

0001

SET

2103

0002

CON

0003

RES

2104

0004

CON

0005

RES

2105

0006

CON

0007

RES

2106

0008

CON

0009

SET

2107

0010

CON

0011

RES

CTH0

0012

LD

2002

0013

CTH

0 2101

0014

CTC

0 #00050

When start/stop of clock pulse is controlled by the input relay which enables/
disables the high-speed counter, response relay of up to 1 scan is generated
at start. Also, the same response relay is generated at stop, which may stop
clock pulse output while the output relay is still ON.

This controls clock pulse so that it always starts and stops when 2105 turns OFF.
Turn ON/OFF special utility relay 2105 as required to enable or disable output of
direct clock pulses using one of the external clocks. Use SET and RES instructions
together or only KEEP instruction to turn ON/OFF this relay.
The diagram below can be added to the sample diagram so that direct clock pulses
are output through 0500 only when 0000 is ON.

CAUTION

When outputting clock pulse with cycle 1 ms (1 kHz) from 0501
This program example shows how to output clock pulse with 1:1 ON/OFF ratio from
0501, through high-speed counter CTH1 and high-speed counter comparator CTC2.

Setting special utility relays

Special utility relays 2203 to 2212 are set as shown on the right table.
The program can be simplified using reverse output (toggle) for pulse with 1:1 ON/
OFF ratio.

Relay No.

Setting

Relay No.

Setting

2203

ON

2212

OFF

2204

OFF

2208

OFF

2205

OFF

2209

OFF

2206

OFF

2210

OFF

2207

ON

2211

OFF