7.2 Serial Communication

3-316

7

Chapter 7 Serial Communication

Subroutines are nested to four levels
or more.

FOR/NEXT instructions are nested to
eight levels or more.

Five levels or more of interrupts
occurred simultaneously.

MPS/MPP instructions are nested to
eight levels or more.

Content in RAM was erased. All data
in data memory and current values of
counters in the KV were cleared.

Scan time exceeds 300 ms.

Attempt was made to operate a KV
base unit which has no programs
stored.

Hardware error was detected in a KV
base unit.

Error code

Description

Cause

Remedy

00

No error

10

CALL nest error

11

FOR nest error

12

INT nest error

13

MPS nest error

20

Memory error

30

Scan timer error

40

NO PROGRAM

50

SND/RTN failure

51

Division by zero

52

Address error

53

Invalid instruction

54

Watchdog timer error

7.2.6

Error Code List

When a "Checking KV PLC error" command (?E) is transmitted, the KV sends back
the error code. The following list shows the description, cause, and remedy for each
error code.

These errors may occur when a
program is executed.

Check the program while paying
particular attention to usage of
subroutines and the INT instruction,
and restore the program accordingly.

Turn the KV off once and turn it on.
Register data from the beginning.

Check the program again.

• Be sure that there is no excessive

repetition using the FOR/NEXT loop.

• Be sure that an interrupt is not

executed at a higher rate.

Write a program into KV.

Turn off the power for the KV, and
then turn it on again. If the cause of
the error is not removed, the KV may
be faulty. Contact your nearest
KEYENCE office.