2.4 Instruction Details

1

2

3-69

Chapter 2 Instructions

Example

Coding

Description

0500 and 0501 turn ON 0.1-s after 0000 turns ON.

TMS is a subtraction timer. When the current value reaches "#00000", the
contact of the timer No. turns ON.

When input relay 0000 turns OFF, contact T000 turns OFF and the current value
of TMS000 is reset.

Note 1: The TMS number cannot be the same as any other TMS, TMH, TMR, C, or
UDC instructions in the same program.

Note 2: The current value of TMS is not retained but is reset to the preset value if
power failure occurs or if power is turned OFF.

When the number specified by TMS is used as a contact (T000 in the above
example), this contact can be used as many times as desired. It can also be
used as both N.O. and N.C. contacts.

Timer accuracy = 0.001 sec. + (1 scan time) (max.)

Operand

Key operations

TMS: 1-ms Timer

Sets a 16-bit on-delay timer that
counts down in 0.01 ms decrements.

*1 0.001 s x 100 = 0.1 s

SET

1

ANB

5

FUN

#ddddd

T

xxx

T
S

0000

T000

0500

#00100

T

000

T

S

Preset value: 0.1 s

Line No.

Instruction

Operand

0000

LD

0000

0001

TMS

000 #00010*

1

0002

LD

T000

0003

OUT

0500

SET

1

ANB

5

FUN

ENT

R-SRCH

ENT

R-SRCH

Operand

(Preset value)

Operand

(TMS No.)

:

TMS

Visual KV

KV-300

KV-10/16

KV-24/40/80

No.: 000 to 249

No.: 000 to 249

No.: 000 to 063

No.: 000 to 119

Preset value:

Preset value:

Preset value:

Preset value:

#00000 to #65535

#00000 to #65535

#00000 to #65535

#00000 to #65535

KVNKA Chap 02_4aP.p65

08.3.11, 11:58 AM

69