background image

4.5 Special Functions Using High-speed Counters

3-229

Visual KV

Series

1

4

Chapter 4 High-speed Counters

Setting method

Set the desired output frequency (Hz) into DM1936. The available range is 16 Hz
to 50 kHz (16 to 50000).

Pulses are output when special utility relay 2306 is ON. The output is stopped
when the relay is turned OFF.

If an unacceptable frequency is specified, special utility relay 2307 (error relay)
turns ON. Special utility relay 2306 is turned OFF and pulse output is stopped.

Note 1: The available minimum frequency specified in DM1936 is 16 Hz.
Note 2: The output is stopped when a value of 15 or less is specified in DM1936.

Note 3: Starts and stops of pulse output or frequency changes are executed after
each scan.

Note 4: It takes a maximum of 200 µs from when the output command is issued until
pulses are output.

Note 5: CTH1 and special utility relays 2200 through 2215 cannot be used when the
specified frequency pulse output function is used.

4.5.2

Applications of the Specified Frequency Pulse Output

Program using a digital trimmer
The following ladder program illustrates how to use a digital trimmer to output pulses
at a desired frequency (16 Hz to 10 kHz).
Pulse output is stopped when the value of the digital trimmer decreases to 15 or
less.

1) Sets the upper limit of the digital trimmer to "10000" and turns ON special utility

relay 2306 to start the specified frequency pulse output.

2) Sets the input value of the digital trimmer as the output frequency value.
3) Output relay 0500 turns ON when a setting error occurs.

2008

0003

0005

#10000

LDA

DM1938

STA

0

TMIN

DM1936

STA

2002

0001

2307

0002

END

ENDH

0004

0500

2306

SET

1)

2)

3)