2.4 Instruction Details

3-174

2

Chapter 2 Instructions

Total count 1
Writes the total count of 4 lines (0000 to 0003) into DM0000.
Reset input relay is 0005.

Coding

Total count 2
Counts the number of boxes transferred on 5 production lines. Produces output
when the number becomes 100 or more.

#00000

LDA

2008

0000

DM0000

STA

0005

#00000

DW

DM0000

INC

0001

DM0000

INC

0002

DM0000

INC

0003

DM0000

INC

DM0000

Clears DM0000 to #00000 when 0005 turns ON.

Sets #00000 to DM0000 at startup.

Increments DM0000 by 1 at UP edge of input relay 0000.

Increments DM0000 by 1 at UP edge of input relay 0001.

Increments DM0000 by 1 at UP edge of input relay 0002.

Increments DM0000 by 1 at UP edge of input relay 0003.

Line No.

Instruction

Operand

0000

LD

2008

0001

LDA

#00000

0002

CON

0003

STA

DM0000

0004

LD

0000

0005

@INC

DM0000

0006

LD

0001

0007

@INC

DM0000

0008

LD

0002

0009

@INC

DM0000

0010

LD

0003

0011

@INC

DM0000

0012

LD

0005

0013

DW

#00000 DM0000

0000

0005

2002

$0000

DW

DM0000

INC

0001

DM0000

INC

0002

DM0000

INC

0003

DM0000

INC

0004

DM0000

INC

DM0000

0500

2009

#00100

DM0000

CMP

LDA

Turns output relay 0500 ON when value
of DM0000 is 100 or more.

Increments DM0000 by 1 at UP edge of
input relay 0000.

Increments DM0000 by 1 at UP edge of
input relay 0001.

Increments DM0000 by 1 at UP edge of
input relay 0002.

Increments DM0000 by 1 at UP edge of
input relay 0003.

Increments DM0000 by 1 at UP edge of
input relay 0004.

Clears DM0000 when input relay 0005
turns ON.

INC / @INC / DEC / @DEC