1.3 Device Configuration

3-22

1

Chapter 1 Programming

1.3.12 Relay Nos. and Functions

Assignment of Relay Nos.
The components of a relay no. are shown below.

■ Unit Nos.
Unit nos. are assigned to units within the KV-300 system, with the unit connected to
the right of the KV-300 CPU (see the figure below) assigned as no. 7. The CPU is
assigned as unit no. 0.

■ Address Nos.
Address nos. are assigned to the input units, output units, and I/O terminal units.
The following table shows the assignment of address nos. to units.

*

The KV-R1A I/O Distribution Unit accommodates 5 input units and 5 output units.
Addresses are set with address switches.

0 7 5 1 5

Address No.

Channel No.

Relay No. (00 to 15)

Module No. (07 to 17)

Input (0 to 4)
Output (5 to 9)

Power supply unit

CPU

0

7

8

9

16

17

Unit

Address No.

KV-300 CPU

CPU

0, 5

KV-C16X

16-input unit

0

KV-C32X

32-input unit

0. 1

KV-B16R

16-output unit

5

KV-B16S

16-output unit

5

KV-C32T

32-output unit

5, 6

KV-R8X

8-input terminal unit

0 to 4 *

KV-R16X

16-input terminal unit

KV-R8R

8-output terminal unit

5 to 9 *

KV-R16R

16-output terminal unit

KV-R8T

8-output terminal unit

KV-R16T

16-output terminal unit