3.3 Direct Input/Output

3-197

Visual KV

Series

1

3

Chapter 3 Interrupts

2002

2008

END

INT

0000

1000

0005

RETI

ENDH

0500

HSP

0000

HSP

0005

EI

1000

SET

2002

2008

EI

END

INT

0000

HSP

0001

HSP

0000

2002

RETI

INT

0001

2002

RETI

ENDH

0500

SET

0501

SET

3.3

Direct Input/Output

This section describes direct input and output.

3.3.1

Direct Input

The direct input function is used during interrupt processing. Direct input allows the

KV PLC to fetch the input status of the input relays during execution of the interrupt
program.

Direct input is available only with input relays 0000 through 0015 (KV-10xx: 0000-
0005, KV-16xx: 0000-0009). (KV-300: 0000-0005)

The input time constant must be set to 10 µs by using the HSP instruction or by
turning ON special utility relay 2813.

The direct input data is effective only within the interrupt program so that the
internal utility relay must be provided.

3.3.2

Direct Output

Direct output allows the Visual KV PLC to output the ON/OFF status of output relays
during execution of the interrupt program. Direct output is available only with output
relays 0500 through 0503.

Direct output is not affected by the scan time.