Setting the upper/lower limit
Turns ON 0500 when the C001 value is 1000 or less.
Turns ON 0501 when the C001 value is 2000 or more.

Coding

Changing the CMP setting value
Compares the current value of counter C000 with the CMP setting value. The setting
value of the CMP instruction is specified with the digital trimmer (TMIN0). The
following example changes the setting value to the range from "0" through "100".
The upper limit of the digital trimmer is set to "100".

0500 turns ON when the current value of C000 is smaller than the CMP setting
value.
0501 turns ON when the current value of C000 is equal to or greater than the CMP
setting value.

Coding

2011

2009

0001

2002

2002

C001≤#01000

C001≥#02000

C001

LDA

C001

LDA

#01000

CMP

#02000

CMP

0500

0501

#09999

0000

C001

Line No.

Instruction

Operand

Line No.

Instruction

Operand

0000

LDB

0001

0008

OUT

0500

0001

C

001 #09999 0000

0009

LD

2002

0002

LD

2002

0010

LDA

C001

0003

LDA

C001

0011

CON

0004

CON

0012

CMP

#02000

0005

CMP

#01000

0013

CON

0006

CON

0014

ANB

2009

0007

ANB

2011

0015

OUT

0501

Sets range of TMIN from 0 to 100.

2009

2009

0001

2002

2002

C000

LDA

DM0000

CMP

DM0000

STA

0

TMIN

0500

0501

#09999

00000

C000

Line No.

Instruction

Operand

Line No.

Instruction

Operand

0000

LD

2002

0011

C

000 #09999 0000

0001

TMIN

0

0012

LD

02002

0002

CON

0013

LDA

C000

0003

ADD

#00001

0014

CON

0004

CON

0015

CMP

DM0000

0005

MUL

#00004

0016

MPS

0006

CON

0017

AND

2009

0007

DIV

#00010

0018

OUT

0500

0008

CON

0019

MPP

0009

STA

DM0000

0020

ANB

2009

0010

LDB

0001

0021

OUT

0501

CMP / @CMP