Output Examples

Examples 1 to 5 are configurable in LCD keypad output programming. Examples 6 to 9 must be configured with the
Director software and Sent to Panel.

Example 1: Simple Single Equation with Follow Output

Bxxx:00 “? D025.00 Query ”

- Schedule 25 is in schedule

Bxxx:01 “T 000 Timer ”

- Follow (Normal)

• Output Bxxx will be ON whenever schedule #25 is in effect.

Example 2: Simple Single Equation with Inverting Output

Bxxx:00 “? D025.00 Query ”

- Schedule 25 is in schedule

Bxxx:01 “T 100 Timer ”

- Inverting Follow Output

• Output Bxxx will be OFF whenever schedule #25 is in effect. Whenever schedule #25 is not in effect, output xxx will

be ON.

Example 3: Simple Single Equation with Timed Output

Bxxx:00 “? D025.00 Query ”

- Schedule 25 is in schedule

Bxxx:01 “T 010 Timer ”

- Timed positive output, 60 seconds

• Output Bxxx will turn on for 60 seconds when schedule 25 first goes into effect.

• E.g. schedule 25 is defined as 9am to 5pm, Monday to Friday. Output xxx will turn on for 60 seconds at 9am on

Monday and then will turn off etc. for the rest of the days of the week assigned.

Example 4: Simple Single Equation with Inverting Timed Output

Bxxx:00 “? D025.00 Query ”

- Schedule 25 is in schedule

Bxxx:01 “T 110 Timer ”

- Timed negative output, 60 seconds

• Output Bxxx will turn off for 60 seconds when schedule 25 first goes into effect and will be on otherwise.

• E.g. schedule 25 is defined as 9am to 5pm, Monday to Friday. Output xxx will normally be ON and will turn off for

60 seconds at 9am on Monday and then will turn back on etc. for the rest of the days of the week assigned.

Example 5: Toggle Output on function Key

Bxxx:00 “? A001.01 Query ”

- Function Key 1 in area 1

Bxxx:01 “T 098 Timer ”

- Toggle output.

• The key term is Timer “Toggle Output” (T098).

• Note that T198 could be entered but this has the same function as T098.

• Pressing Function key 1 in area 1 turns the output ON. Repeating this procedure turns it off.

Example 6: Simple Two Term AND Equation with Normal Output

Configurable only with Director software and Sent to Panel

Bxxx:00 “? D025.00 Query ”

- Schedule 25 is in schedule

Bxxx:01 “? A002.14 Query ”

- Area 2 is OFF

Bxxx:02 “L 01 Logic ”

- Logical AND operator

– additional screen generated with Director software.

Bxxx:03 “T 000 Timer ”

- Follow (Normal)

additional screen generated with Director software.

• Output Bxxx will turn on when schedule 25 is in effect AND area 2 is off. Otherwise, output xxx will be off.

• *** This equation can not be created directly at the LCD Keypad – it would have to be created in the Director

software. After the logical operation and timer value conditions have been made in the Director software and sent to
the panel, modifying them can be done at the keypad but not any other changes.

• *** This equation can not be deleted from the LCD keypad directly. Values for the first term (Bxxx:0) can not be