Polarity of output assign – Nor-Cal SDC15 Controller User Manual

Page 106

Advertising
background image

Polarity of output assign

The polarity of four output assigns (A, B, C, D) used for the output bit function
can be set.

• When the object control output is the relay output or voltage pulse output, and

the operation type of the DO Assignment is set for output bit functions 1 to 4, the
display and setting can be made.

• When the object event output is provided and the operation type of the DO

Assignment is set for output bit functions 1 to 4, the display and setting can be
made.

Handling Precautions

The output relay may be turned ON and OFF repeatedly at a high-

speed depending on the conditions.

To avoid such faulty operation, always strictly observe the following

cautions:

Control output 1: When any of [Output assign A, B, C, D] (ot1.2 to

ot1.5) is set at [49: Control output 1 status], do not set [1: Reverse]

for the same symbol of [Output assign A, B, C, D Polarity].

Event output 1: When any of [Output assign A, B, C, D] (ev1.2 to

ot1.5) is set at [48: Event output 1 status], do not set [1: Reverse] for

the same symbol of [Output assign A, B, C, D Polarity].

5-56

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Control output 1 Polarity A
to D (Setup setting/DO
Assignment bank)

The digits are called 1st digit, 2nd digit, 3rd
digit, and 4th digit from the right end.

1st digit: Output assign A Polarity setting
2nd digit: Output assign B Polarity setting
3rd digit: Output assign C Polarity setting
4th digit: Output assign D Polarity setting

0: Direct
1: Reverse

0000

High function

Control output 2 Polarity A
to D (Setup setting/DO
Assignment bank)

0000

Event output 1 Polarity A to
D (Setup setting/DO
Assignment bank)

0000

Event output 2 Polarity A to
D (Setup setting/DO
Assignment bank)

0000

Event output 3 Polarity A to
D (Setup setting/DO
Assignment bank)

0000