Decimal point position

When the PV input type is L (DC voltage/DC current) or when the PV input type

is a part of the PV input range type of R (RTD), the decimal point position of the

PV input can be set.

Handling Precautions

As this setting is changed, the decimal point position of the parameters

related to the decimal point position of the PV input is also changed.

Actually, the decimal point position of the following settings are

changed:

SP setting

SP low limit/high limit setting

SP up ramp/down ramp setting

Event setting and continuous output setting related to PV

Event setting and continuous output setting related to SP

Event setting and continuous output setting related to deviation

(absolute deviation)

Note

• For the display conditions, setting range and initial value of range numbers

(C01), refer to:

5-1 (PV Input), PV range tables.(on page 5-2).

5-4

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Output after PV square root extraction (PVout)

100%FS

PVin

Dropout value (variable change from 0.1 to 100.0%)

0

100%FS

0

Y = Xin/100 X100

Item (Setting display/bank)

Display

Contents

Initial value

User level

Decimal point position
(Setup setting/Setup bank)

0: No decimal point
1: 1 digit below decimal point
2: 2 digits below decimal point
3: 3 digits below decimal point

0

Simple,
Standard,
High function