Nor-Cal SDC15 Controller User Manual

Page 111

Advertising
background image

5-61

Example 2 The operation is started by the external switch, and then it is stopped

automatically 30 min. after the temperature has reached the set value.

Explanation

The timer start-up conditions are set to logical AND of DI1 and PV status EVs.
The ON delay time setting of the timer becomes the time, at which the operation is
stopped automatically after the temperature has reached the set value.
The mode (RUN/READY) is changed based on a combination of DI1 and timer
ON-OFF.

Setting example

• Event

Note. The internal event No. is indicated at the mark of "x" shown in the Display

column.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Set value

Time

30min

Control ON

Control OFF

Temperature

Status

Control OFF

Timer counting after

Operation stop by

status

starting of operation

time-up

DI1

OFF

ON

ON

Timer (Internal EV2)

OFF

OFF

ON

Status of Internal

ON

OFF

ON

Contact 2

Mode

READY

RUN

READY

Event

Display

Internal Event 1

Internal Event 2

Operation type

Ex.C1

32: Timer

4: Deviation high limit

Direct/reverse

Ex.C2

----

0: Direct

Standby

Ex.C2

----

0: No standby

EVENT state at READY

Ex.C2

0: EVENT state at READY

0: EVENT state at READY

is continued.

is continued.

Alarm OR

Ex.C3

0: None

0: None

Special OFF setup

Ex.C3

----

0: As usual.

Delay time unit

Ex.C3

2.1min

0: 0.1s

Event main setting

Ex

----

0

(low limit)

Event sub setting

Ex.SB

----

----

(high limit)

Hysteresis

Ex.HY

----

5

ON delay

Ex.ON

30

0

OFF delay

Ex.OF

0

0