Parameter bank, Bank selection – Nor-Cal SDC15 Controller User Manual

Page 140

Advertising
background image

6-6

Chapter 6. LIST OF DISPLAYS AND SETTING DATA

Parameter bank

Bank selection:

Display

Item

Contents

Initial
value

User
level

Remarks

Control method

0: ON/OFF control
1: Fixed PID
2: ST (Self-tuning)

0

or

1

0

The initial value is “0” when
control output 1 is relay
output. The initial value is “1”
in other cases.

MV low limit at AT

-10.0 to +110.0%

0.0

0

Displayed when the control
method is other than the
ON/OFF control (CtrL

0).

MV high limit at AT

-10.0 to +110.0%

100.0

0

Differential
(for ON/OFF control)

0 to 9999U

5

0

Displayed when the control
method is other than the
ON/OFF control (CtrL

0).

ON/OFF control
action point offset

-1999 to +9999U

0

2

PV filter

0 to 120.0s

0.0

0

PV ratio

0.001 to 9.999

1.000

1

PV bias

-1999 to +9999U

0

0

Time proportional
cycle unit 1

0: Unit of “1s”
1: Fixed at “0.5s”.

(Cycle time setting is disabled.)

2: Fixed at “0.2s”.

(Cycle time setting is disabled.)

3: Fixed at “0.1s”.

(Cycle time setting is disabled.)

0

2

Displayed when MV1 (time
proportional output (heat) of
Heat/Cool control) is
connected to the relay
control output, voltage pulse
output, or event output in the
DO Assignment.
The initial value of Time
proportional cycle 1 is “10”
when the control output is the
relay output. The initial value
is “2” in other cases.

Time proportional
cycle 1

5 to 120s (Output includes the relay
output.)
1 to 120s (Output does not include
the relay output.)

10

or

2

0

Time proportional
cycle unit 2

0: Unit of “1s”
1: Fixed at “0.5s”

(Cycle time setting is disabled.)

2: Fixed at “0.2s”.

(Cycle time setting is disabled.)

3: Fixed at “0.1s”.

(Cycle time setting is disabled.)

0

2

Displayed when the
Heat/Cool control is used
(C26=1) and MV2 (time
proportional output (heat) of
Heat/Cool control) is
connected to the relay
control output, voltage pulse
control output, or event
output.
The initial value of Time
proportional cycle 2 is “10”
when the model has one
control output point. The
initial value is “2” in other
cases.

Time proportional
cycle 2

5 to 120s (Output includes the relay
output.)
1 to 120s (Output does not include
the relay output.)

10

or

2

0

Time proportional
cycle mode

0: Controllability aiming type
1: Operation end service life aiming

type (Only one ON/OFF operation
within Time proportional cycle)

0

or

1

2

The initial value is “1” when
control output 1 is the relay
output. The initial value is “0”
in other cases.

SP up ramp

0.0 to 999.9U
(No ramp when set at “0.0U”)

0.0

2

Time unit of the ramp is
selected by the SP ramp unit
(C32).

SP down ramp

0.0

2

Displayed under the same
conditions as

CY

except that a

relay is not included in the
output.

Displayed under the same
conditions as

CY2

except that

a relay is not included in the
output.