User function bank, Lock bank, Bank selection – Nor-Cal SDC15 Controller User Manual

Page 157

Advertising
background image

6-23

Chapter 6. LIST OF DISPLAYS AND SETTING DATA

User Function bank

Bank selection:

Lock bank

Bank selection:

Display

Item

Contents

Initial
value

User
level

Remarks

User Function 1

Each setting is set on the upper display.
The following shows the setting
exceptions:

----

: Not registered.

P--

: Proportional band of currently

used PID group

I--

: Integral time of currently used

PID group

d--

: Derivative time of currently

used PID group

rE--

: Manual reset of currently

used PID group

OL--

: Output low limit of currently

used PID group

OH--

: Output high limit of currently

used PID group

P--C

: Proportional band for cool

side of currently used PID
group

I--C

: Integration time for cool side

of currently used PID group

d--C

: Derivative time for cool side

of currently used PID group

OL.-C

: Output low limit for cool side

of currently used PID group

OH.-C

: Output high limit for cool side

of currently used PID group

----

1

User Function 7

----

1

User Function 2

----

1

User Function 3

----

1

User Function 4

----

1

User Function 5

----

1

User Function 6

----

1

It is possible to register only
the settings, which can be
displayed.
(Example: Manual reset of
the PID constant can be
registered when the I
(Integral time) is set at “0”.)
The registered setting is
added to the end of the
display order of the basic
display.

User Function 8

----

1

Display

Item

Contents

Initial
value

User
level

Remarks

Key lock

0: All settings are possible.
1: Mode, event, operation display,

SP, UF, lock, manual MV, and
mode key can be set.

2: Operation display, SP, UF, lock,

manual MV, and mode key can be
set.

3: UF, lock, manual MV, and mode

key can be set.

0

0

Password 1A

0000 to FFFF (Hexadecimal value)

0000

0

Communication lock

0

2

Loader lock

0: Loader communication read/write

enabled.

1: Loader communication read/write

disabled.

0

2

Password display

0 to 15
5: Password 1A to 2B display

0

0

When two sets of passwords
(1A and 1B, 2A and 2B) are
matched, the setting is
possible.
[mode] key operation, MV
setting in MANUAL mode,
key lock, password display,
and password 1A to 2B can
be set when the key lock
(LoC) is a value of 0 to 3.

Displayed when the
password display (PASS) is
“5” and two sets of
passwords (1A and 1B, 2A
and 2B) are matched.

0: RS-485 communication read/write

enabled.

1: RS-485 communication read/write

disabled.

Password 2A

0000 to FFFF (Hexadecimal value)

0000

0

Password 1B

0000 to FFFF (Hexadecimal value)

0000

0

Displayed when the
password display (PASS) is
“5”.

Password 2B

0000 to FFFF (Hexadecimal value)

0000

0