Control action and Heat/Cool control

The control action (direct/reverse) and Heat/Cool control (enabled/disabled) can
be selected.

• When the control method is other than the ON/OFF control (CtrL ≠ 0),

[Heat/Cool control: C26] can be displayed and set.

• When the Heat/Cool control is set disabled (C26 = 0), [Control action: C14] can

be displayed and set.

• When the Heat/Cool control is set enabled (C26 = 1), the control action is

changed to the reverse action (C14 = 0), the preset MANUAL value (C20) is
changed to "50.0", and the initial output of PID control (C22) is changed to
"50.0".

• The reverse action (heat control) is a control that decreases (or turns OFF) the

manipulated variable (MV) as the PV increases.
The direct action (cool control) is a control that increases (or turns ON) the
manipulated variable (MV) as the PV increases.

■

Special control outputs

The control output at PV alarm and control output at READY can be set.

• When the control method is other than the ON/OFF control (CtrL ≠ 0) and the

Heat/Cool control is set enabled (C26 = 1), [Output at READY (cool): C18] can
be displayed and set.

• The PV alarm status means that AL01, 02, or 03 occurs.

5-12

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Control action
(direct/reverse)
(Setup setting/Setup bank)

0: Heat control (Reverse)
1: Cool control (Direct)

0

Simple,
Standard,
High function

Heat/Cool control
(Setup setting/Setup bank)

0

Simple,
Standard,
High function

0: Disabled.
1: Enabled.

Item (Setting display/bank)

Display

Contents

Initial value

User level

Output operation at PV
alarm
(Setup setting/Setup bank)

0: Control calculation is continued.
1: Output at PV alarm is output.

0

High function

Output at PV alarm
(Setup setting/Setup bank)

0.0%

High function

-10.0 to +110.0%

Output at READY (Heat)
(Setup setting/Setup bank)

0.0%

Standard,
High function

-10.0 to +110.0%

Output at READY (Cool)
(Setup setting/Setup bank)

0.0%

Standard,
High function

-10.0 to +110.0%