Nor-Cal SDC15 Controller User Manual

Page 46

Advertising
background image

4-8

Chapter 4. WIRING

2. Omron's G3PA, G3PB, G3NA

• Input current:

Since the input current is 7mA or less, up to three units (7mA
X 3 = 21mA < 24mA [maximum allowable current]) can be
connected in parallel.

• Operating voltage range (input):

The rating voltage is 5 to 24Vdc or 12 to
24Vdc. Therefore, the voltage between the
terminals is within the range.

Voltage between terminals (three G3PA units)

= Open voltage - internal resistance X total drive current
= 19Vdc ±15% - 82Ω ±0.5%

X 21mA

14 to 20V

Connection diagram

Number of connectable units

(Note) 3 units for each output

=

This unit

+

+

G3PA

+

G3PA

+

G3PA

SSR to be used

Connection

V0/VC model

VV model

Omron G3PA

Parallel connection

Up to 3 units

Up to 6 units (Note)

Omron G3PB

Parallel connection

Up to 3 units

Up to 6 units (Note)

Omron G3NA

Parallel connection

Up to 3 units

Up to 6 units (Note)