Chapter 8. modbus communications functions, 1 outline of communications, Features – Nor-Cal SDC15 Controller User Manual

Page 175: Setup, 8 - 1 outline of communications

Advertising
background image

Chapter 8.

MODBUS COMMUNICATIONS FUNCTIONS

8 - 1

Outline of Communications

8-1

If the optional model number is provided with the RS-485 communications function, communications with a PC,

PLC or other host devices are available using a user-prepared program.

The communications protocol can be selected from the CPL communications (Controller Peripheral Link:

Yamatake's host communications protocol) and the MODBUS communications. This chapter describes the

MODBUS communications.

Features

The features of the SDC15's communications functions are as follows:

• Up to 31 SDC15 units can be connected to a single master station as a host

device.

• When the communications specifications of the host device conform to the RS-

232C interface, the communications converter CMC10L (sold separately) is

required.

The

CMC10L allows you to perform the conversion between RS-232C and RS-

485.

• Almost all of the parameters held by the device can be communicated.

For details on communications parameters,

refer to

Chapter 9, LIST OF COMMUNICATION DATA

.

Setup

The following setups are required for performing the MODBUS communications:

• If the optional model number is provided with the RS-485 communications

function, display and setup are available.

• If the communications type is set to MODBUS RTU format, data format (data

length) cannot be displayed nor set up, and the action is fixed to 8-bit data.

Handling Precautions

• Setups can be performed through key operation on the console or the

smart loader package SLP-C35. However, they cannot be performed
via RS-485 communications.

• If you use the Yamatake CMC10L as an RS-232C/RS-485 converter,

set the response time-out (C70) to 3 ms or longer.

Item

Display

Contents

Initial User

(Setting display/bank)

value

level

CPL/MODBUS

0: CPL

0

Simple,

(Setup setting/Setup bank)

1: MODBUS ASCII format

Standard,

2: MODBUS RTU format

High

Station address

0: Does not communicate

0

function

(Same as above)

1 to 127

Transmission speed

0: 4800bps

2

(Same as above)

1: 9600bps
2: 19200bps
3: 38400bps

Data format (Data length)

0: 7-bit

1

(Same as above)

1: 8-bit

Data format (Parity)

0: Even parity

0

(Same as above)

1: Odd parity
2: No parity

Data format (Stop bit)

0: 1 stop bit

0

(Same as above)

1: 2 stop bits

Response time-out

1 to 250 ms

3

High
function