Chapter 2.

OUTLINE OF FUNCTIONS

2 - 1

Input/Output Configuration

2-1

PV input

Sensor or range is selected for the PV input. The selection range may vary

depending on the input type of the model (T: Thermocouple, R: RTD, L: DC

current, DC voltage).

Control output

When the control output type of the model is “R: Relay” or “V: Voltage pulse”,

the control output becomes the ON-OFF control output or time proportional

output. When the time proportional output is used, the time proportioning cycle

time can be set. When the control output type of the model is “C: Current”, the

control output becomes the continuous output (analog output). When the model

has two control outputs, the heat/cool control can be used only with "Simple

configuration".

Event output

When the model provides the event, the alarm or control mode set in [Event type]

can be output as DO (digital output).

DI (digital input)

When the model provides the DI, the function set with the DI assignments can be

selected.

CT (current transformer) input

When the model provides the CT input, the heater burnout alarm can be output

from the event output.

Other

Digital
output

process

Analog

output

process

Control output 1, 2
(Current output)

Control output 1, 2
(Relay output, voltage
pulse output)

Event output 1 to 3
(Relay output)

CT input 1, 2

Digital input 1, 2

PV input

PV

process

Internal

event

process

Control

process

(ON/OFF

control,

PID control)

Other

Other

Internal

contact

process

CT

process