Handling Precautions

• Do not allow the current to exceed the upper limit of the CT input display

range. Doing so might cause a malfunction.

• If a current exceeding the upper limit of the CT input display range is

detected, the CT input failure alarm (AL11) is displayed. However, if the

excessive current is very large, the CT input failure alarm is not

displayed.

• The CT input display range and measurement current range change

according to the number of CT turns and the number of CT power wire

loops. Set for the number of CT turns and the number of CT power wire

loops suitable for the conditions of the CT connected. The display range

and the measurement current range are calculated by the formulas

shown below. (The internal calculations of this device have an error of

less than 0.1A.)

Display range lower limit (A) = 0.0

Display range upper limit (A) = Number of turns ÷ (16 x number of

power wire loops) x 1.4

Measurement current range lower limit (A) = Number of turns ÷ (2000 x

number of power wire loops)

Measurement current range upper limit (A) = Number of turns ÷ (16 x

number of power wire loops)

The table below shows examples of how display range and measurement

current range change according to the number of CT turns and the number

of CT power wire loops. Measurement current range is shown in

parentheses.

• If ROM version 1 of the instrument information bank (

Id02

) is prior to

version 2.04, the operation is always performed on the basis of 800 CT

turns and one CT power wire loop. The number of CT1/CT2 turns and

power wire loops is not displayed and cannot be set.

• If ROM version 1 of the instrument information bank (

Id02

) is prior to

version 2.04, the CT input failure alarm (AL11) is not displayed.

5-72

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

100 turns

400 turns

800 turns

1600 turns

4000 turns

1 time

0.0 to 8.7A

0.0 to 35.0A

0.0 to 70.0A

0.0 to 140.0A 0.0 to 350.0A

(0.1 to 6.2A) (0.2 to 25.0A) (0.4 to 50.0A) (0.8 to 100.0A) (2.0 to 250.0A)

2 times

0.0 to 4.3A

0.0 to 17.5A

0.0 to 35.0A

0.0 to 70.0A

0.0 to 175.0A

(0.1 to 3.1A) (0.1 to 12.5A) (0.2 to 25.0A) (0.4 to 50.0A) (1.0 to 125.0A)

6 times

0.0 to 1.4A

0.0 to 5.8A

0.0 to 11.6A

0.0 to 23.3A

0.0 to 58.3A

(0.1 to 1.0A) (0.1 to 4.1A)

(0.1 to 8.3A) (0.2 to 16.6A) (0.4 to 41.6A)

Number of

turns

Number of

power wire

loops

Advertising