12 continuous output, Output range, Output type – Nor-Cal SDC15 Controller User Manual

Page 116: 5 - 12 continuous output

Advertising
background image

5 - 12

Continuous Output

5-66

The following shows the functional block diagram of the continuous output:

Output range

The output range of the current output can be set.

• When the object control output is the current output, the display and setting can
be made.

Output type

The output type of the current output can be set.

• When the object control output is the current output, the display and setting can

be made.

• MV scalable bandwidth is used to calculate SP+PV and PV+MV. For details,

refer to MV scaling range (on page 5-68).

• If ROM version 1 of the instrument information bank is prior to 2.04, SP+MV

and PV+MV cannot be selected.

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

(Setting: Setup C42, C47)

Continuous output (current output)

Output range type

(Setting: Setup C43, C48)

Output type

(Setting: C44, C45, C49 to C50)

Output scaling high limit/low limit

Item (Setting display/bank)

Display

Contents

Initial value

User level

Control output 1 range
(Setup setting/Setup bank)

1: 4 to 20mA
2: 0 to 20mA

1

Simple,
Standard,
High function

Control output 2 range
(Setup setting/Setup bank)

1

Item (Setting display/bank)

Display

Contents

Initial value

User level

Control output 1 type
(Setup setting/Setup bank)

0: MV (manipulated variable)
1: Heat MV (for heat/cool control)
2: Cool MV (for heat/cool control)
3: PV
4: PV before ratio, bias, and filter
5: SP
6: Deviation (PV-SP)
7: CT1 current value
8: CT2 current value
9: MFB (Invalid on SDC15)
10: SP+MV
11: PV+MV

0

Simple,
Standard,
High function

Control output 2 type
(Setup setting/Setup bank)

3