2 list of parameter setting displays, Mode bank, Sp bank – Nor-Cal SDC15 Controller User Manual

Page 137: 6 - 2 list of parameter setting displays

Advertising
background image

6-3

Chapter 6. LIST OF DISPLAYS AND SETTING DATA

6 - 2

List of Parameter Setting Displays

The following shows the meanings of the values stated in the “User Level” column:

0: Simple, Standard, or High function configuration, 1: Standard or High function configuration, and 2: High

function configuration

Mode bank

Bank selection:

SP bank

Bank selection:

Display

Item

Contents

Initial
value

User
level

Remarks

AUTO/MANUAL

AUto: AUTO mode
MAn: MANUAL mode

AUTO

0

RUN/READY

RUN

0

Displayed when the control
method is other than the
ON/OFF control (CtrL

0).

Whether or not this item is
displayed is selected by the
display mode setup (C73).

rUn: RUN mode
rdy: READY mode

Whether or not this item is
displayed is selected by the
display mode setup (C73).

AT stop/start

AT

stop

0

At.oF: AT stop
At.on: AT start

Displayed when the control
method is other than the
ON/OFF control (CtrL

0).

Whether or not this item is
displayed is selected by the
display mode setup (C73).

Release all DO
latches

Latch

con-

tinue

0

Lt.on: Latch continue
Lt.oF: Latch release

All DO latches such as
control outputs (relay and
voltage pulse) and event
outputs can be released.
Whether or not this item is
displayed is selected by the
display mode setup (C73).

Communication DI

OFF

0

dI.oF: OFF
dI.on: ON

Whether or not this item is
displayed is selected by the
display mode setup (C73).

Display

Item

Contents

Initial
value

User
level

Remarks

SP of LSP 2 group

0

0

SP of LSP 1 group

0

0

Displayed when LSP system
group (C30) is "2" or more.

SP low limit (C07) to SP high limit
(C08)

SP of LSP 3 group

0

0

Displayed when LSP system
group (C30) is "3" or more.

SP of LSP 4 group

0

0

Displayed when LSP system
group (C30) is "4" or more.