Alarm OR, special OFF setup, and delay time unit

Alarm OR, special OFF setup, and delay time unit accompanying with the
operation type can be set.

• When the internal event configuration 1 operation type is set at [0: No event], the

internal event configuration 3 (alarm OR, special OFF setup, and delay time unit)
is not displayed.

The following shows the relationship among alarm OR setting, alarm present/not
present, and internal event ON/OFF:

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Internal Event 1
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)

The digits are called 1st digit, 2nd digit, 3rd
digit, and 4th digit from the right end.
1st digit: Alarm OR setup

0:

None

1:

Alarm direct + OR operation

2:

Alarm direct + AND operation

3:

Alarm reverse + OR operation

4:

Alarm reverse + AND operation

2nd digit: Special OFF setup

0:

As usual.

1:

When EV main setting is “0”, the
event is set to “OFF”.

3rd digit: Delay time unit setup

0:

0.1s

1:

1s

2:

1 min.

4th digit: Undefined.

0:

Undefined.

0000

High function

0000

Internal Event 2
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)

0000

Internal Event 3
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)

0000

Internal Event 4
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)

0000

Internal Event 5
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)

None

Not present

OFF

OFF

Not present

ON

ON

Present.

OFF

OFF

Present.

ON

ON

Alarm direct +

Not present

OFF

OFF

OR operation

Not present

ON

ON

Present.

OFF

ON

Present.

ON

ON

Alarm direct +

Not present

OFF

OFF

AND operation

Not present

ON

OFF

Present.

OFF

OFF

Present.

ON

ON

Alarm reverse +

Not present

OFF

ON

OR operation

Not present

ON

ON

Present.

OFF

OFF

Present.

ON

ON

Alarm reverse +

Not present

OFF

OFF

AND operation

Not present

ON

ON

Present.

OFF

OFF

Present.

ON

OFF

Alarm OR setting

Alarm (AL01 to
99) present/not

present

Internal event

ON/OFF status before

alarm OR process

Internal event

ON/OFF status after

alarm OR process