3 list of setup setting displays, Setup bank, 6 - 3 list of setup setting displays – Nor-Cal SDC15 Controller User Manual

Page 142

Advertising
background image

6-8

Chapter 6. LIST OF DISPLAYS AND SETTING DATA

6 - 3

List of Setup Setting Displays

The following shows the meanings of the values stated in the “User Level” column:

0: Simple, Standard, or High function configuration, 1: Standard or High function configuration, and 2: High

function configuration

Initial value may depending on model No.

Setup bank

Bank selection:

Display

Item

Contents

Initial
value

User
level

Remarks

PV input range type

When the PV input type is
thermocouple (T): 1 to 6, 9 to 11, 13
to 21, 24, 25

1

0

For details, refer to the PV
Input Range Table (on page
5-2).

When the PV input type is RTD (R):
41 to 46, 51 to 54, 63, 64, 67, 68

41

When the PV input type is DC
voltage/DC current (L): 84, 86 to 90

88

Temperature unit

0: Celsius (°C)
1: Fahrenheit (°F)

0

0

Displayed when the PV input
type is thermocouple (T) or
RTD (R).

Cold junction
compensation (T/C)

0: Cold junction compensation (T/C)

is performed (internal).

1: Cold junction compensation (T/C)

is not performed (external).

0

2

Displayed when the PV input
type is thermocouple (T).

Decimal point position

0: No decimal point
1: 1 digit below decimal point
2: 2 digits below decimal point
3: 3 digits below decimal point

0

0

Displayed when the PV input
type is DC voltage/DC
current (L) or RTD having the
range with the decimal point.

PV input range low
limit

When the PV input type is
thermocouple (T) or RTD (R), the
input range low limit selected with the
PV input range type (C01) is
displayed, but the setting is disabled.

0

When the PV input type is DC
voltage/DC current, a value ranging
from –1999 to +9999 is set.

PV input range high
limit

When the PV input type is
thermocouple (T) or RTD (R), the
input range low limit selected with the
PV input range type (C01) is
displayed, but the setting is disabled.

0

When the PV input type is DC
voltage/DC current, a value ranging
from –1999 to +9999 is set.

0

1000

SP low limit

PV input range low limit to PV input
range high limit

1

SP high limit

1

PV square root
extraction dropout

0.0 to 100.0
(PV square root extraction is not
performed when set at “0.0”.)

0.0

2

Displayed when the PV input
type is DC voltage/DC
current (L).

Control action
(Direct/Reverse)

0: Heat control (Reverse action)
1: Cool control (Direct action)

0

0

Output operation at
PV alarm

0: Control calculation is continued.
1: Output at PV alarm is output.

0

2

Output at PV alarm

-10.0 to +110.0%

0.0

2

Output at READY
(Heat)

-10.0 to +110.0%

0.0

1

Output at READY
(Cool)

-10.0 to +110.0%

0.0

1

Displayed when the control
method is other than the
ON/OFF control (CtrL

0) and

the heat/cool control (C26 =
1) is used.