Event channel def.

When the operation type is the timer start/stop, a target Event channel can be set.

• When the operation type of the same internal contact No. is set at “Timer

stop/start”, the display and setting can be made.

■

Input bit function

Four kinds of input bit functions are provided. What function of four functions is
used or is not used can be set.

• When the set value is “0”, the input bit function is not used and the default input

is used. The following shows the default input of each internal contact:

Internal Contact 1: DI (digital input) 1
Internal Contact 2: DI (digital input) 2
Internal Contact 3: OFF status

• In the input bit function, the logical operations (AND, OR) of each of internal

contacts 1 to 3 are combined. In input bit functions 1 to 4, the combination of the
logical operations may vary. The following shows one logical operation:

Logical AND

Logical OR

OFF and OFF = OFF

OFF or OFF = OFF

ON and OFF = OFF

ON or OFF = ON

ON and ON = ON

ON or ON = ON

• “OFF” is “contact open (OPEN)” or “0” when expressed using the numerical

value.

• “ON” is “contact close (CLOSE)” or “1” when expressed using the numerical

value.

5-34

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

Internal Contact 1 Event
channel def.
(Setup setting/DI
Assignment bank)

0: Every Internal Event
1 to 5: Internal Event number

0

High function

0

Internal Contact 2 Event
channel def.
(Setup setting/DI
Assignment bank)

0

Internal Contact 3 Event
channel def.
(Setup setting/DI
Assignment bank)

Item (Setting display/bank)

Display

Contents

Initial value

User level

Internal Contact 1 Input bit
function
(Setup setting/DI
Assignment bank)

0: Not used (Default input)
1: Function 1 ((A and B) or (C and D))
2: Function 2 ((A or B) and (C or D))
3: Function 3 (A or B or C or D)
4: Function 4 (A and B and C and D)

0

High function

0

Internal Contact 2 Input bit
function
(Setup setting/DI
Assignment bank)

0

Internal Contact 3 Input bit
function
(Setup setting/DI
Assignment bank)