• The following describes examples showing how to use the ON/OFF control

action point offset:
To turn OFF the output at 205˚C or more and turn ON the output at less than
190˚C with the heat control and SP = 200˚C, the differential is set to 15˚C and
the offset is set to 5˚C.
To turn OFF the output at 5˚C or less and turn ON the output at more than 10˚C
with the cool control and SP = 10˚C, the differential is set to 5˚C and the offset is
set to -5˚C.

PID control

In the fixed PID control or ST (self-tuning), the PID control related items can be
set.

5-14

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

P (Proportional band)
(Parameter setup/PID
bank)

0.1 to 999.9%

5.0%

Simple,
Standard,
High function

I (Integral time)
(Parameter setup/PID
bank)

120s

0 to 9999s
(No integration control action when set at "0".)

D (Derivative time)
(Parameter setup/PID
bank)

30s

0 to 9999s
(No derivative control action when set at "0".)

Manual reset
(Parameter setup/PID
bank)

50.0%

-10.0 to +110.0%

MV low limit
(Parameter setup/PID
bank)

-10.0 to +110.0%

0.0%

Standard,
High function

MV high limit
(Parameter setup/PID
bank)

-10.0 to +110.0%

100.0%

P (Proportional band) (cool)
(Parameter setup/PID
bank)

0.1 to 999.9%

5.0%

Simple,
Standard,
High function

I (Integral time) (cool)
(Parameter setup/PID
bank)

0 to 9999s
(No integration control action when set at "0".)

120s

D (Derivative time) (cool)
(Parameter setup/PID
bank)

0 to 9999s
(No derivative control action when set at "0".)

30s

Output low limit (Cool)
(Parameter setup/PID
bank)

-10.0 to +110.0%

0.0%

Standard,
High function

Output high limit (Cool)
(Parameter setup/PID
bank)

-10.0 to +110.0%

100.0%