Temperature unit

When the PV input type is T (thermocouple) or R (RTD), the temperature unit can
be selected.

• When the PV input type is T (thermocouple) or R (RTD), the display and setting

can be made.

Cold junction compensation (T/C)

When the PV input type is T (thermocouple), any of the following can be selected:

• The cold junction compensation (T/C) is performed inside this unit.
• The cold junction compensation (T/C) is not performed inside this unit since

an external cold junction compensation unit, such as ice bath is used.

• When the PV input type is T (thermocouple), the display and setting can be

made.

PV square root extraction dropout

When the PV input type is L (DC voltage/DC current), a dropout value can be set
so that the result of the PV square root extraction used to convert the pressure
(differential pressure) into the flow becomes "0".
• When the PV input type is L (DC voltage/DC current), the display and setting

can be made.

• Details of PV square root extraction

The calculation input in % and the calculation result in % are expressed as PVin
and PVout, respectively.
When the PV input is the PV square root extraction dropout set value or more
and less than 100.0%, the control formula becomes as shown below.

PVout = √PVin ÷ 100 X 100

When the PV input is larger than 0.0% and smaller than the PV square root
extraction dropout set value, PVout = 0.0%.
When the PV input is 0.0% or less or 100.0% or more, the square root extraction
is not performed. Therefore, PVout = PVin.

Item (Setting display/bank)

Display

Contents

Initial value

User level

5-3

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Temperature unit
(Setup setting/Setup bank)

0: Celsius (˚C)
1: Fahrenheit (˚F).

0

Simple,
Standard,
High function

Item (Setting display/bank)

Display

Contents

Initial value

User level

Cold junction
compensation (T/C)
(Setup setting/Setup bank)

0: Cold junction compensation (T/C) is

performed (internal).

1: Cold junction compensation (T/C) is not

performed (external).

0

High function

Item (Setting display/bank)

Display

Contents

Initial value

User level

PV square root extraction
dropout
(Setup setting/Setup bank)

0.0%: Square root extraction is not performed.
0.1 to 100.0%

0.0%

High function