4 at (auto tuning) function, Starting procedures, Stopping procedures – Nor-Cal SDC15 Controller User Manual

Page 71: 5 - 4 at (auto tuning) function

Advertising
background image

5 - 4

AT (auto tuning) Function

5-21

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

The AT (auto tuning) function is used in the following cases:
• The PID constants are set automatically with the control method set at “Fixed PID” ([CtrL = 1]).
• The PV rise is slow or overshoot is large in the control with the PID constants, which have been set automatically

using the ST function.

• The PV rise becomes slow or overshoot becomes large with the control method set at ST ([CtrL] = 2).

The AT function can be used when the control method is set at either “Fixed PID” ([CtrL] = 1) or ST ([CtrL = 2]).

Starting procedures

(1) Make sure that the PV input or operation end (heater power, etc.) is

controllable.

(2) Make sure that the mode indicator [rdy] is off and the operation is in the RUN

mode. If the indicator [rdy] is lit and the operation is in the READY mode,
change the mode to the RUN mode.

(3) Make sure that the mode indicator [man] is off and the operation is in the

AUTO mode. If the indicator [man] is lit and the operation is in the MANUAL
mode, change the mode to the AUTO mode.

(4) Set the parameter setting [AT Stop/Start] to “AT start ([At] = [At.on])”.

Stopping procedures

The AT function is completed automatically. To stop the AT function, which is
running, change the parameter setting [AT Stop/Start] to AT stop ([At] = [At.oF]).
Additionally, the AT function is stopped when changing the READY mode to the
MANUAL mode.

Display during execution of AT

The decimal point at the 1st digit of the display No. 1 (right end digit) flashes
twice repeatedly while the AT function is running. When the AT function is
completed and the PID constants are changed, this LED goes off.

Operation during execution of AT

The AT function calculates the PID constants using the limit cycle.

(1) When the AT function is started, a point, where the SP and PV deviations are

split to “2:1”, is determined as ON/OFF change point of the MV (manipulated
variable).

(2) When the limit cycle is judged as stable, the PID constants are changed and the

AT function is completed.