5 numeric representation in the application layer – Nor-Cal SDC15 Controller User Manual

Page 171

Advertising
background image

7 - 5

Numeric Representation in the Application Layer

The specifications of numeric representation are decimal variable-length (zero suppress) for RS and WS commands

and hexadecimal fixed-length for RD, WD, RU and WU commands. Details are as follows:

RS and WS commands

RD, WD, RU and WU commands

7-13

Chapter 7. CPL COMMUNICATIONS FUNCTIONS

Item

Specifications

Remedies

Unwanted space

Cannot be appended.

Unwanted zero

Cannot be appended.

Numerical value = zero

Cannot be omitted.
Be sure to use "0".

Other unwanted

Numerical values may be prefixed

characters

with a "-" expressing a negative
number. Any other character cannot
be appended. The "+" sign must not
be appended to indicate positive
numerical values.

Range of available

-32768 to +32767

numerical values

Values out of this range are not
allowed.

The message processing is aborted
and an abnormal termination code
is returned as a response message.

Item

Specifications

Remedy

Unwanted space

Cannot be appended.

Unwanted zero

Cannot be appended.

Numerical value = zero

Cannot be omitted.
Be sure to use "0000".

Other unwanted

Cannot be appended.

characters

Range of available

0000H to FFFFH

numerical values

The message processing is aborted
and an abnormal termination code
is returned as a response message.