Nor-Cal SDC15 Controller User Manual

Page 60

Advertising
background image

5-10

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

MV1 = MV

Fixed PID

Control method: Fixed PID

(Setting: Parameter CtrL

must be set at "1".)

ST

Control method: ST (Self-tuning)

(Setting: Parameter CtrL

must be set at "2".)

Adjustment according to

step response/hunching

(Setting: Extended tuning

St.SA, St.Sb, St.Hb, St.Ud)

ST is not run in the following cases:

• Heat/Cool control is used.
• Just-FiTTER is used.

READY mode

AUTO mode

MANUAL mode

RUN mode

SP lag overshoot suppression

(Setting: Extended tuning SP.Lg)

RationaLOOP high precision

control logic

(Setting: Extended tuning Ctr.A)

Just-FiTTER overshoot suppression

(Setting: Extended tuning

JF.ov, JF.bd)

Bumpless transfer/Preset selection

(Setting: Setup C19, C20)

Branching according to

AUTO/MANUAL mode

Branching according to

RUN/READY mode

MV

MV1 = MV

Branching according to

output operation at PV alarm

(Setting: Setup C15, C16)

PID control

(Setting: PID P-1, I-1, d-1, rE-1,

oL-1, oH-1, P-1.C, I-1.C, d-1.C,

oL-1.C, oH-1.C)

Output at PV alarm

(Setting: Setup C16)

Branching according to

Heat/Cool control

(Setting: Setup C26)

C26 = 0

C26 = 1

Branching according to

Heat/Cool control

(Setting: Setup C26)

MV1 = Heat MV

MV2 = Cool MV

MV1 = Heat MV

MV2 = Cool MV

Output at READY

(Setting: Setup C17, C18)

Heat/Cool control

(Setting: Setup C28, C29)

Output at READY

(Setting: Setup C17)

PV is correct or

C15 = 0:

C26 = 0

C26 = 1

PV is faulty and C15 = 1: