11 application examples, Examples of applications using assign functions, 5 - 11 application examples – Nor-Cal SDC15 Controller User Manual

Page 109

Advertising
background image

5 - 11

Application Examples

This section describes examples of applications using the assign functions of this unit.

■

Examples of applications using assign functions

The following shows setting examples with the Smart Loader Package

SLP-C35

.

To use assign functions, it is absolutely necessary to set the user level to “High
function configuration”.

●

Example 1 Logical OR of the heater burnout and PV high limit alarm is output.

Conditions: PV high limit is set to Internal Event 1.

Heater burnout is set to Internal Event 2.
Logical OR of the above events is output to the EV1 relay.

(1) Select

[Standard]

→

[Event]

and set

[Internal Event 1]

to

[1: PV high limit]

.

(2) Similarly, set

[Internal Event 2]

to

[16: Heater 1 break/Heater over

current]

.

(3) Select

[Option]

→

[DO Assignment]

and right-click on the operation type of

[Event output 1]

to select

[Input/Output port setup]

.

5-59

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION