Chapter 10. MAINTENANCE AND

TROUBLESHOOTING

10-1

Maintenance

Cleaning

When removing the dirt from the measuring instrument, wipe it off with a soft

cloth rag. At this time, do not use any organic solvent, such as paint thinner or

benzene.

Part replacement

Do not replace any parts of this unit.

Fuse replacement

When replacing the fuse connected to the electric wiring, always use the specified

standard fuse.

Standard

IEC127

Shut-down speed

Slow-action type (T)

Rated voltage

250V

Rated current

200mA

Alarm displays and corrective action

The following Table shows the alarm displays and corrective actions if any failure

occurs in this unit:

Alarm code

Failure name

Cause

Corrective action

PV input failure

Sensor burnout, incorrect wiring,

(Over-range)

incorrect PV input type setting

PV input failure

Sensor burnout, incorrect wiring,

(Under-range)

incorrect PV input type setting

CJ failure

Terminal temperature is faulty
(thermocouple).

PV input failure

Sensor burnout, incorrect wiring Check the wiring.

(RTD)
CT input failure

A current exceeding the upper

(over-range)

limit of the display range was

(CT input 1 or 2,

measured. The number of CT

or both)

turns or the number of CT
power wire loops is incorrectly
set, or wiring is incorrect.

A/D conversion

A/D converter is faulty.

failure

Parameter failure

Data is corrupted by noise, or
power is shut-down while the
data is being set.

Adjustment data

Data is corrupted by noise, or

failure

power is shut-down while the
data is being set.

Parameter failure

Data is corrupted by noise.

(RAM area)

Adjustment data

Data is corrupted by noise.

failure (RAM area)

ROM failure

ROM (memory) is faulty.

Check the wiring.
Set the PV input type
again.

Check the ambient
temperature.

Replace the unit.

• Restart the unit.
• Set the data again (set

data for AL95/97 and
adjustment data for
AL96/98).

• Replace the unit.

• Restart the unit.
• Replace the unit.

• Use a CT with the correct

number of turns for the
display range.

• Reset the number of CT

turns.

• Reset the number of CT

power wire loops.

• Check the wiring.

Handling Precautions

• If ROM version 1 of the instrument information bank (

Id02

) is prior to

2.04, CT input failure (AL11) is not displayed.