Nor-Cal SDC15 Controller User Manual

Page 212

Advertising
background image

13-4

Chapter 13. SPECIFICATIONS

●

Isolation between input and output

Portions enclosed by solid lines are insulated from other signals.

Whether or not inputs and outputs are provided may vary depending on the model.

✽

In case of the independent contacts, the output 1 and the output 2 are isolated.

●

Environment conditions
• Standard conditions

Ambient temperature: 23±2˚C
Ambient humidity:

60±5%RH

Power supply voltage: AC power model, 105Vac±1%, 50/60Hz±1Hz

DC power model, 24Vac±1%, 50/60Hz±1Hz

24Vdc±5%

Vibration:

0m/s

2

Shock:

0m/s

2

Mounting angle:

(Reference plane) ±3˚

• Operating conditions

Ambient temperature: 0 to 50˚C (0 to 40˚C for tight-mounting)
Ambient humidity:

10 to 90%RH (No condensation allowed.)

Power supply voltage: AC power model, 85 to 264Vac, 50/60Hz±2Hz

(Rating: 100 to 240Vac, 50/60Hz)
DC power model, 21.6 to 26AVac, 50/60Hz±2Hz/21.6 to 52.8Vdc
(Rating: 24Vac, 50/60Hz 24 to 48Vdc)

Vibration:

0 to 2m/s

2

(10 to 60Hz for 2 hrs. in each of the X-, Y-, and Z-direction)

Shock:

0 to 10m/s

2

Mounting angle:

(Reference plane) ±10˚

• Transportation conditions

Ambient temperature: -20 to +70˚C
Ambient humidity:

10 to 95%RH (No condensation allowed.)

Power supply

Control output 1

PV input

Control output 2

CT input 1

Internal circuit

CT input 2

Event output 1

✽

Loader communication

Event output 2

✽

Digital input 1

Event output 3

Digital input 2

RS-485 communication