13 ct (current transformer) input, 5 - 13 ct (current transformer) input – Nor-Cal SDC15 Controller User Manual

Page 119

Advertising
background image

5-69

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

5 - 13

CT (Current Transformer) Input

For CT input, two kinds of current values are provided.
• Current value at output ON.: This current value is used for the heater burnout/over-current event. This current

value is displayed as CT current value.

• Current value at output OFF.: This current value is used for the heater short-circuit event. This current value

cannot be displayed.

When [CT type] is set at “heater burnout detection” (C36 = 0 or C39 = 0), the following operation is performed:
The current value at output ON becomes the CT current value measured when the output specified in [CT output]
is turned ON.
The current value at output OFF becomes the CT current value measured when the output specified in [CT output]
is turned OFF.
When [CT type] is set at “current value measurement” (C36 = 1 or C39 = 1), the following operation is performed:
The current value at output ON becomes the measured CT current value regardless of the output ON/OFF status.
The current value at output OFF is fixed at “0.0A”.

The following shows the functional block diagram of the CT (current transformer) input:

Handling Precautions

The current value at output ON is used when the operation type of the

Internal Event is set at [heater burnout/over-current].

The current value at output OFF is used when the operation type of the

Internal Event is set at [heater short-circuit].

(Setting: Setup C36, C39)

Current value at output ON

Current value at output OFF

Current value at output ON.

Current value at
output OFF = 0A

CT type

(Setting: Setup C37, C40)

Monitoring of output status

(ON/OFF)

(Setting: Setup C38, C41)

Wait before measurement

Operation: Heater burnout detection

Output is ON.

Output is OFF.

Operation: Current value measurement