5-17

ST (Self-tuning)

The following ST related items can be set:

• When the control method is set at ST (CtrL = 2), the display and setting can be

made.

• Function of ST step execution resolution width (St.SA)

When the % value of the SP change width to the PV range is larger than the set
value, the ST is started with the step response.

• Function of ST step settling width (St.Sb)

When the % value of the absolute value deviation to the PV range is smaller than
the set value, this is judged as that the step response is settled in ST.

• Function of ST hunting settling width (St.Hb)

When the PV moves up or down so that the % value of the absolute value
deviation to the PV range becomes larger than the set value, this is judged as
hunching, and then the ST is started. After that, the % value of the absolute value
deviation to the PV range becomes smaller than the set value, this is judged as
that the hunching is settled.

Handling Precautions

• For details about self-tuning, refer to

5-5 ST (Self-tuning) Function (on page 5-24)

5-6 Precautions for ST (Self-tuning) (on page 5-26)

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

Item (Setting display/bank)

Display

Contents

Initial value

User level

ST step execution
resolution width
(Parameter setup/Extended
tuning bank)

0.00 to 99.99%

10.00%

High function

ST step settling width
(Parameter setup/Extended
tuning bank)

0.0 to 10.00%

0.50%

ST hunting settling width
(Parameter setup/Extended
tuning bank)

0.0 to 10.00%

1.00%

ST step ramp change
(Parameter setup/Extended
tuning bank)

0: ST is executed when the PV moves up or

down.

1: ST is executed only when the PV moves

up.

0