Mode display setup – Nor-Cal SDC15 Controller User Manual

Page 124

Advertising
background image

5-74

Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

MODE display setup

Whether or not the mode related setup items of the parameter setting and mode
bank are displayed can be set.

• When using the Smart Loader Package

SLP-C35

, not only the numeric value,

but also the bit input can be used to set [MODE display setup: C73].

Handling Precautions

• Even though the AUTO/MANUAL display is set at [Displayed], the

AUTO/MANUAL is not displayed when [CtrL: Control method] is set at

“0” (ON/OFF control).

• Even though the AT stop/start display is set at [Displayed], the AT

stop/start is not displayed when [CtrL: Control method] is set at “0”

(ON/OFF control).

Item (Setting display/bank)

Display

Contents

Initial value

User level

MODE display setup
(Setup setting/Setup bank)

Whether or not the mode bank setup is
displayed is determined by the sum of the
following weights:
Bit 0: AUTO/MANUAL display

Disabled: 0, Enabled: +1

Bit 1: RUN/READY display

Disabled: 0, Enabled: +2

Bit 3: AT stop/start display

Disabled: 0, Enabled: +8

Bit 4: Release all DO latches display

Disabled: 0, Enabled: +16

Bit 5: Communication DI1 ON/OFF display

Disabled: 0, Enabled: +32

Other invalid settings, 0, +4, +64, +128

255

Standard,
High function

2

7

2

6

2

5

2

4

2

3

2

2

2

1

2

0

Undefined.

Undefined.

Communication DI1 ON/OFF display

Release all DO latches display

AT stop/start display

Undefined.

RUN/READY display

AUTO/MANUAL display

Advertising