Event configuration bank – Nor-Cal SDC15 Controller User Manual

Page 147

Advertising
background image

6-13

Chapter 6. LIST OF DISPLAYS AND SETTING DATA

Event configuration bank

Bank selection:

Display

Item

Contents

Initial
value

User
level

Remarks

Internal Event 1
Configuration 1
Operation type

0: No event
1: PV high limit
2: PV low limit
3: PV high/low limit
4: Deviation high limit
5: Deviation low limit
6: Deviation high/low limit
7: Deviation high limit

(Final SP reference)

8: Deviation low limit

(Final SP reference)

9: Deviation high/low limit

(Final SP reference)

10: SP high limit
11: SP low limit
12: SP high/low limit
13: MV high limit
14: MV low limit
15: MV high/low limit
16: CT1 heater burnout/over-current
17: CT1 heater short-circuit
18: CT2 heater burnout/over-current
19: CT2 heater short-circuit
20: Loop diagnosis 1
21: Loop diagnosis 2
22: Loop diagnosis 3
23: Alarm (status)
24: READY (status)
25: MANUAL (status)
26: Invalid
27: During AT execution (status)
28: During SP ramp (status)
29: Control direct action (status)
30: During ST execution (status)
31: Invalid
32: Timer (status)
33: High and low limits of MFB value

(Invalid in this unit)

0

0

Internal Event 1
Configuration 2

The digits are determined to 1st digit,
2nd digit, 3rd digit, and 4th digit from
the right end.

0000

0

1st digit: Direct/
Reverse

0: Direct
1: Reverse

2nd digit: Standby

0: None
1: Standby
2: Standby + Standby at SP change

3rd digit: EVENT state

at READY

0: Continue
1: Forced OFF

4th digit: Undefined

0

Handling Precautions

• If ROM version 1 of the instrument information bank (

Id02

) is prior to

2.04, “33” cannot be set as [Internal Event configuration 1 operation
type].