Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION

User Function

Up to eight selected settings can be added to the operation display.

• Only settings which can be displayed can be registered. (For example, manual

reset of the PID constant can be registered only if integral time (I) is set at 0.)

• Setting cannot be made from the console by using a parameter number displayed

on the setup screen of the PC loader program (

SLP-C35

).

• The following keys can be used to select a parameter to be set:

[<]

key:

Moves to the top parameter of the next parameter bank.

[ ]

key:

Displays the next parameter.

[ ]

key:

Displays the previous parameter.

[enter]

key: Executes the start and confirmation of a setting change.

• When using the Smart Loader Package

SLP-C35

, [User Function] can be

registered even though the conditions for instrument status are set as display

disabled.

Handling Precautions

Settings registered as user functions are displayed as if the user level

is High function, in spite of the actual user level setting in setup C79.

Otherwise the display is according to the C79 setting.

<

<

Item (Setting display/bank)

Display

Contents

Initial value

User level

User Function 1
(Setup setting/User
Function bank)

Each setting is set on the upper display.
The following:

----

: Not registered.

P--

: Proportional band of currently used

PID group

I--

: Integral time of currently used PID

group

d--

: Derivative time of currently used PID

group

rE--

: Manual reset of currently used PID

group

OL--

: Output low limit of currently used PID

group

OH--

: Output high limit of currently used PID

group

P--C

: Proportional band for cool side of

currently used PID group

I--C

: Integration time for cool side of

currently used PID group

d--C

: Derivative time for cool side of

currently used PID group

OL.-C

: Output low limit for cool side of

currently used PID group

OH.-C

: Output high limit for cool side of

currently used PID group

----

Standard,
High function

User Function 2
(Setup setting/User
Function bank)

----

User Function 3
(Setup setting/User
Function bank)

----

User Function 4
(Setup setting/User
Function bank)

----

User Function 5
(Setup setting/User
Function bank)

----

User Function 6
(Setup setting/User
Function bank)

----

User Function 7
(Setup setting/User
Function bank)

----

User Function 8
(Setup setting/User
Function bank)

----

Advertising