Chapter 6.

LIST OF DISPLAYS AND SETTING DATA

6 - 1

List of Operation Displays

6-1

The following shows the meanings of the values stated in the “User Level” column:

0: Simple, Standard, or High function configuration, 1: Standard or High function configuration, and 2: High

function configuration

Operation displays

Display

Item

Contents

Initial
value

User
level

Remarks

Upper display: PV
Lower display: SP

SP (Target value)

SP low limit (C07) to SP high limit
(C08)

0

0

Whether or not this item is
displayed is selected by the
PV/SP display setup (C74).

(Display
example)
Lower display:
LSP

LSP group number
(Numeric value at 1st
digit = the right end
digit)

1 to LSP system group (C30, Max. 4)

1

0

Displayed when LSP system
group (C30) is “2” or more.
The lower display shows the
LSP set value corresponding
to the LSP group number.
Whether or not this item is
displayed is selected by the
PV/SP display setup (C74).

MV (Manipulated
Variable)

-10.0 to +110.0%
Setting is disabled in AUTO mode.
(Numeric value does not flash.)
Setting is enabled in MANUAL mode.
(Numeric value flashes.)

0

In the ON/OFF control (CtrL
= 0), "100.0" is displayed at
ON and "0.0" is displayed at
OFF. Whether or not this
item is displayed is selected
by the MV display setup (C75).

Heat MV (Manipulated
Variable)

Setting is disabled.

0

This item is displayed when
using the Heat/Cool control
(C26 = 1).
Whether or not this item is
displayed is selected by the
MV display setup (C75).

Cool MV (Manipulated
Variable)

Setting is disabled.

0

Upper display:
PV

AT progress display
(Numeric value at the
1st digit = right end
digit)

Setting is disabled.
1 or more : During execution of AT

(Value is decreased.)

0: Completion of AT

0

Displayed during execution of
AT. (The display is continued
even after completion of AT.)
Whether or not this item is
displayed is selected by the
MV display setup (C75).

CT (Current trans-
former) current value 1

Setting is disabled.

0

Displayed when the optional
model has two current
transformer points.
Whether or not this item is
displayed is selected by the
CT display setup (C78).

CT (Current trans-
former) current value 2

Setting is disabled.

0

Internal Event 1
main setting

The allowable setting range may vary
depending on the operation type of
the internal event.
-1999 to +9999U: Set value is other
than the following values:
0 to 9999U: Set value is an absolute
value.
-199.9 to +999.9%: Set value is MV.

0

0

Setting required by the
operation type of the internal
event is displayed.
Whether or not this item is
displayed is selected by the
EV display setup (C76).

Internal Event 1
sub setting

0

0

Internal Event 1
remaining time

Setting is disabled.
“ ” is displayed at the right end digit
when using the ON delay time.
“L” is displayed at the right end digit
when using the OFF delay time.

L

0

Whether or not this item is
displayed is selected by the
timer remain time display
setup (C77).

Internal Event 2
main setting

The allowable setting range may vary
depending on the operation type of
the internal event.
-1999 to +9999U: Set value is other
than the following values:
0 to 9999U: Set value is an absolute
value.
-199.9 to +999.9%: Set value is MV.

0

0

Setting required by the
operation type of the internal
event is displayed.
Whether or not this item is
displayed is selected by the
EV display setup (C76).

Internal Event 2
sub setting

0

0

Internal Event 2
remaining time

Setting is disabled.
“ ” is displayed at the right end digit
when using the ON delay time.
“L” is displayed at the right end digit
when using the OFF delay time.

L

0

Whether or not this item is
displayed is selected by the
timer remain time display
setup (C77).

(Display
example)

(Display
example)

(Display
example)