3 fuse replacement, 4 control module return options – Flowserve MX Limitorque User Manual

Page 116

Advertising
background image

Limitorque MX Maintenance and Spare Parts FCD LMENIM2314-00 – 07/08

108

STEP 14

NOTE: The face of the CP may be installed in any one of four 90° incremental positions. When
changing CP position, avoid over-twisting the ribbon cable.

Rotate the CP until the display orientation of
the front face is correct for normal viewing, and
then slide the CP assembly into the actuator
housing.

14

5.3.2 Removal

For removal, follow installation instructions in reverse.

5.3.3 Fuse Replacement

The view below shows the control module with the chassis assembly removed.

Figure 5.8 – Location of Fuses and Voltage Jumper

Secondary

Fuse

Voltage Jumper

Primary Fuses

Primary Fuse
Remove plastic covers, fuse, and replace with 1 A, 600 V fuse.

Secondary Fuse
Remove plastic cover, fuse, and replace with a 0.1 A, 250 V fuse.

Voltage jumper selection
Remove and replace in proper slots according to nameplate voltage.

5.3.4 Control Module Return Options

Please contact factory for return instructions.