Limitorque MX Maintenance and Spare Parts FCD LMENIM2314-00 – 07/08

126

STEP 3

Disconnect black, blue and brown wires (L1, L2
and L3) from back of terminal block.

3

STEP 4

Disconnect the lead seal from the reverser by unplugging the 2-pin and single-pin white connectors.

STEP 5

Disconnect and remove the encoder mounting screws and the encoder.

STEP 6

Remove the mounting screws for the reverser package and remove the reverser by moving the
reverser towards the space previously occupied by the encoder. Discard the used reverser package.

STEP 7

On the new reverser connect the 2-pin and single-pin white connectors to the lead seal.

STEP 8

Connect the black, blue and brown wires (L1,
L2 and L3) to the back of the terminal block.

8

STEP 9

Install the terminal block with the O-ring and the retaining ring. Install the terminal cover and
screws.

a

CAUTION: While and after installing, keep wires away from cutout. This cutout allows
non-restricting actuation of the reverser plunger.