Limitorque MX Maintenance and Spare Parts FCD LMENIM2314-00 – 07/08

118

STEP 6

Feed the terminal block harness plugs over
the contactor assembly (in the control module
compartment) while removing the terminal
block from the terminal block compartment.

NOTE: An O-ring (#1-20) is included with the
terminal block assembly. Ensure you retain or
replace the O-ring at remounting.

6

1-20

5.8.2 Remounting

STEP 7

c

WARNING: Hazardous Voltage! Turn off all power sources to actuator before remounting
terminal block assembly. Power sources may include main power or control power.

If necessary, to allow terminal block wiring
bundle to pass across the end of the contactor
and into the controls compartment, use a M3
hex key to loosen the two 4 mm contactor
screws (#8-28). Pull contactor assembly off
the screws and lower assembly to create extra
space for the wire harness to pass over the
contactor and into the controls compartment.

7

8-28

STEP 8

Plug power leads L1, L2, and L3 from contactor
assembly into terminal connectors L1, L2, and
L3 on back of terminal block. Verify that the
O-ring (#1-20) is installed on back of terminal
block. Lightly lubricate O-ring before installing
the terminal block.

8

Power

Leads

1-20

Advertising